|
| TM 11-5820-918-13
Place BAT switch to ON position.
o.
p. With the transmitter sweeping and the battery supply on, perform a transmitter
self test by pressing TEST switch. Two functions are checked.
(1) In the system test, a go/no-go indication is provided for determining oper-
ation of the synthesizer and power supplies. If the SYST green indicator lamp lights,
operation is correct. If the SYST red lamp lights, a malfunction is indicated. Refer
to the maintenance procedures of Section 5 for instructions to correct fault.
(2) (Applicable to units with non-rechargeable battery supply, P/N 6025-1008
only). The condition of the standby battery supply is also checked when the TEST
switch is actuated. If only the green BAT test lamp lights, the battery voltage is
23 volts or greater which is the acceptable condition. If both the green and red BAT
lamps light, the condition of the battery is marginal but operational (voltage between
18 and 23 volts). If only the red BAT lamp lights, the battery voltage is 18 volts
or lower, and the battery (18 alkaline D-cells) must be replaced.
(3) (Applicable to units with rechargeable battery supply, P/N 6025-1018 only).
The condition of the battery supply and charging circuit is also checked when the
TEST switch is activated. If only the green BAT lamp lights, the battery supply is
satisfactory (not fully discharged) and the charging circuit is operating. If the red
lamp or both red and green lamps light, the possible indications are: the BAT switch
is OFF; the battery supply or charging circuit is malfunctioning; or the battery sup-
ply is fully discharged. To check the actual charge of the battery, refer to proce-
dure in paragraph 5-26.
performance of the start-up procedures, routine operator actions are performed in
coordination with, and usually at the direction of the RCS-4B receiver operator. Typ-
ical operations are as follows:
a. With the sweep and clock started, place MODE switch in PROG position. The
frequency sweep will advance from 2 MHz to the upper limit of either 16 or 30 MHz
(as selected by the UPPER FREQ switch) in each five minute period of the hour. The
individual five-minute periods are enabled or disabled by the path programmer MIN -
UTES switches. If a particular MINUTES switch is down, disabling the transmitter
sweep, the frequency display remains at 02.00 MHz and there is no transmitted signal
for that 5-minute interval. The transmitter MIN/SEC clock continues to run.
b. A transmitter self-test can be performed at any time and has no effect on trans-
mitter operation. Refer to step p, paragraph 3-7 above for description of self test
procedure.
c. Proper forward and reflected power can be measured at any time. In DIPLEX
with the FWD/REFL switch on the 1024 front panel in the FWD position, the needle
should remain in the green zone; with the switch in the REFL position, the needle
should remain below the red zone. In DIRECT mode, the measurement of forward and
reflected power may vary considerably depending on the load impedance of the an-
tenna. Meter readings inside and outside colored zones can be expected during nor-
mal opertion. As a general guide, if the forward power indication is in the green zone,
and the reflected power indication is below the red zone, then the VSWR is less than
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |