|
| TM 11-5820-695-35
(2) The traffic monitor signal is supplied by
lamp DS1 assembly off, causing failure lamp DS1 to be
radio transmitter modulator 1A8 through attenuator
extinguished. When the sawtooth signal is not present
assembly 1A3. The traffic monitor signal is applied
or its amplitude drops to a low level, the ac detector
directly to operational amplifier (integrated circuit) AR1.
biases the transistor in failure lamp DS1 assembly on,
The operational amplifier output is detected and applied
causing failure lamp DS1 to light red (alarm condition).
to the traffic meter through a potentiometer and to
Pressing the TEST button on electrical frequency
Schmitt trigger circuit Q5, Q6 through dc emitter
synthesizer 1A14 front panel applies 5 vdc to the failure
follower Q1. If the traffic monitor signal exceeds a
lamp transistor causing the lamp to light red.
predetermined level, the dc voltage developed by the
detector CR1 and CR2 will cause Q5 to turn on, causing
(4) Voltage regulator Q02 provides 20 vdc to
Q6 to turn off and Q7 to turn on. With Q7 turned on, a
operate transistor circuits Q3 through Q6 and Q8
low impedance path to ground is provided for the normal
through Q13.
traffic indicator lamp, and the TRAF indicator lights
green. Since Q6 is turned off, a high impedance path to
2-14.
Alarm-Monitor
1A5
Block
Diagram
ground is provided for the alarm traffic indicator lamp
Description (fig. 5-14)
causing the indicator lamp (red) to remain off. When
the traffic monitor signal falls below the predetermined
a.
Alarm monitor 1A5 receives monitor
voltage, the dc voltage applied to the base of Q5 is not
signals (traffic monitor, forward rf power monitor,
sufficient to keep Q5 conducting. With Q5 turned off,
reflected rf power monitor, and synthesizer monitor
Q6 turns on and Q7 turns off. For this condition, a high
signals) and controls the associated alarm indicators on
impedance path to ground is applied to the normal
transmitter meter panel assembly 1A15A8. Depending
traffic indicator lamp and a low impedance path to
upon the signal level received, the associated indicator
ground is applied to the alarm traffic indicator lamp.
lights either green (normal indication) or red (alarm
Consequently, the TRAF indication changes from green
indication). The alarm monitor also contains a summary
to red. Also with Q7 turned off, the Q7 output dc
alarm circuit which is enabled when any one of the
voltage is high, enabling the OR gate which causes Q23
alarm conditions occur. The traffic monitor signal
to turn on. With Q23 turned on, a transmitter summary
indicates the signal level input to radio transmitter
alarm indication is provided.
modulator 1A8. The forward rf power monitor and
reflected rf power monitor signals indicate the power
(3) The synthesizer monitor signal is derived
levels at the output of the T-1054/GRC-144. The
from electrical frequency synthesizer 1A14. The signal
synthesizer monitor signal is received directly from
(dc level) is applied directly to Schmitt trigger Q14, Q15.
electrical frequency synthesizer 1A14 and indicates if
Circuit operation is identical to that described above for
the signals from variable 2 frequency divider 1A14A5
the traffic monitor circuit. If the synthesizer monitor
and standard radio frequency oscillator 1A14A7 are
signal exceeds the predetermined dc level, the SYNTH
phase locked. An identical alarm monitor 2A12 is used
LOCK indicator lights green (normal indication). If the
in the R-1467/GRC-144; however, the jumper
synthesizer monitor signal is below the predetermined
connections on the associated plate assembly
level, the SYNTH LOCK indicator lights red (alarm
connectors are different for each assembly. Alarm
condition) and, in addition, the summary alarm circuit is
monitor 2A1,2 is described in paragraph 2-24.
enabled.
b.
The following description is based on the
(4) The forward rf power monitor signal is a
circuits shown in figure 5-14.
detected dc voltage supplied by directional coupler
1DC1. The dc signal is applied to operational amplifier
(1) The TRAF, RF POWER, REFL RF
(integrated circuit) AR3 and the meter selector switch on
POWER, and SYNTH LOCK indicators on the meter
meter panel assembly 1A15A8 through an attenuator.
panel assembly 1A16A8 are controlled by Schmitt
The output of AR3 is applied directly to Schmitt trigger
trigger circuits in alarm monitor 1A5. The Schmitt
Q11, Q12. The operation of the Schmitt trigger is
trigger circuits cause the associated indicators to light
Identical to that described above for the traffic monitor
green (normal indication) or red (alarm condition). The
circuit. If the rf power monitor signal exceeds the
input signals to the alarm monitor control the operation
predetermined dc level, the RF
of the associated Schmitt trigger circuits.
2-41
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |