Click here to make tpub.com your Home Page

Page Title: CHAPTER 9. REGULATOR, VOLTAGE CN-1214/g
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home

   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 



TM 11-5820-554-12
CHAPTER 9
REGULATOR, VOLTAGE CN-1214/g
Section I. INTRODUCTION
5 percent) for any combination of rated line and for a
9-1. Description
load from 1.0 to 0.8 power factor lagging.
Regulator, Voltage CN-1214/G (Superior Electric Type
b. Use. Regulator, Voltage CN-1214/G is intended
IE525001) is mounted in a gray enamel, louvered
for use with fixed radio station equipment.
cabinet. On the recessed front panel are an amber pilot
9-3. Tabulated Data
light which indicates that the unit is energized; a control
circuit fuse; a double-pole, single-throw circuit breaker
Input voltage
80.5 to 149.5 volts a.c.
48 to 63 Hz.
to energize and protect the unit; a screwdriver
Output voltage
115 volts a.c.
adjustment control to vary the output voltage; and six
5 percent.
Regulation
output connector receptacles to connect the output to
Power factor
1.0 to 0.8 lagging.
the load. The input terminal board is behind an access
Response time
400 milliseconds.
Minimum load
0.675 kilovolt ampere at unity power
plate in the lower right-hand corner at the rear of the
factor.
unit. Components are accessible for authorized repair
through the removable top cover, which is fitted with
Kilowatt efficiency at full-  80 percent minimum.
lifting eyebolts at each corner to facilitate lifting by the
load unit power factor and
use of a chain hoist.
an input of 115 vac, 60 Hz.
Kilowatt efficiency at all
70 percent minimum.
9-2. Purpose and Use
other combinations of
a. Purpose.  Regulator, Voltage CN-1214/G is
rated input line and load.
designed to maintain an output voltage (115 volts
Distortion
12 percent rms maximum at rated
alternating current (a.c.) root mean square (rms)
line and load.
Temperature range:
Operating
0' F. to +125F.
Nonoperating
-20F. to +160F.
9-4. Items Comprising an Operable Regulator, Voltage CN-1214/G
Dimensions
Weight
NSN
Item
Qty
Height
Depth
Width
(lb)
Regulator, Voltage CN-1214/G (Superior Electric
1
17 1/8
21 5/8  20 7/8
260
Type
1ES25001).
(approx)
Running spares:
Fuse, 1 amp, slo-blow
5
Lamp, neon type NE-51
1
9-1


Privacy Statement - Press Release - Copyright Information. - Contact Us