(14) Eliminate all reflective material from the vicinity of the beam path (TB
MED 524, paragraphs 318, 322.b and 327.a; CECOMR 38510, paragraph 8.l).
(15) Interlocks shall be installed into Class 4 laser laboratory facilities in order
to prevent exposure of personnel entering the lab. Equip door interlocks with a positive
action manual reset device to preclude accidental restart of the laser when the door is
again closed (ANSI Z136.11993 paragraph 4.3.10.2).
(16) ANSI Z136.11993 paragraph 4.4.1; TB MED 524 paragraphs 318 and
319; AR 38563, and MILHDBK 828 have detailed safety procedures for an outdoor
laser range. Local SOPs will prescribe, at a minimum, the following procedures:
(a) Conduct outdoor laser operations at an approved laser range (ANSI
Z136.11993, paragraph 3.4.3; TB MED 524, paragraphs 35.a and 35.b).
(b) Appoint a Laser Range Safety Officer (LRSO) for each laser range
(ANSI Z136.11993, paragraph 1.3.1; TB MED 524, paragraph 34).
(c) Only those personnel and objects approved by the LRSO are permitted
on a laser range between the laser and the target (ANSI Z136.11993, paragraph
1.3.2.7; TB MED 524, paragraphs 34, 35.a and 35.b).